e2.2
Recycles Exceeded — flame sensed then lost
This code typically points to
- Flame established then lost during run
- Weak flame sense
- Gas pressure fluctuation
- Rough ignition
Next checks to confirm
- Measure flame current under run conditions
- Verify gas pressure stability
- Verify ignition carryover
Escalation
One-hour lockout after 10 times
Reset behavior
One-hour lockout per public table.
Urgent
Fix now