Fault Code Lookup

HVAC Sales Master
3
Inducer or Pressure Switch Error
This code typically points to
  • Inducer fault
  • Pressure-switch fault

Next checks to confirm
  1. Check pressure switch closing/opening behavior
  2. Verify inducer operation

Escalation
In 2nd stage: inducer fault forces transition to 1st stage for 10 minutes before retry. In 1st stage: system shuts down and waits 30 seconds before attempting first-stage reestablishment.
Reset behavior
Automatic retry per above; full lockout reset if needed.
Urgent
Fix now
Source
Trane 18-CD26D1-13 Installer's Guide, p.42-43