Suction line transducer validation formula
Field validation formula for suction-pressure transducer: PSIG = 375 × (VDC out / VDC in) - 8.1
This code typically points to
  • Used when validating suspected suction transducer error

Next checks to confirm
  1. Measure VDC in at red/black wires at back of transducer harness
  2. Measure VDC out at green/black wires at back of transducer harness
  3. Calculate: PSIG = 375 × (VDC out / VDC in) - 8.1
  4. Compare calculated PSIG to actual refrigerant gauge reading

Escalation
None; field diagnostic aid
Reset behavior
Not applicable.
Informational
No action needed
Source
Rheem RP18AZ Installation Instructions sensor-checking section