5 blinks
Twinning fault
This code typically points to
  • Thermostat wire on twin terminal
  • Incorrect board switch setting
  • Mismatched boards in twinned furnaces
  • Transformers out of phase
  • Thermostat/wiring issue

Next checks to confirm
  1. Verify twin wiring only between TWIN terminals
  2. Confirm both IFCs are same part number
  3. Verify transformers are in phase
  4. Remove thermostat wires and jumper R to W to isolate thermostat/wiring fault if needed

Escalation
Fault blocks correct twinned operation until configuration/wiring issue is corrected
Reset behavior
Clears when twinning wiring/configuration is corrected; normal operation resumes after fault removal.
Urgent
Fix now