3 blinks
Limit circuit open
This code typically points to
  • Open main high limit due to low airflow or overfired heat exchanger
  • Tripped manual-reset rollout
  • Blocked flue or heat exchanger
  • Poor limit-circuit connection
  • Blocked-drain-switch interaction on upflow 90+ can also indirectly produce flame-failure/lockout behavior

Next checks to confirm
  1. Check filter/airflow restrictions
  2. Inspect registers/dampers
  3. Verify temperature rise and firing rate
  4. Inspect rollout/manual-reset limits
  5. Inspect flue/heat exchanger
  6. Inspect limit wiring and continuity

Escalation
Heating sequence interrupted while limit circuit remains open; may participate in later one-hour lockout behavior on newer generations
Reset behavior
Clears when limit circuit is restored; manual-reset rollout must be physically reset; blocked-drain issue requires trap/drain correction rather than blind board reset.
Safety Critical
Immediate concern
Source
Rheem Gas Furnace FAQ; Rheem 90RS/90RT/90TS Installation Instructions troubleshooting text