Fault Code Lookup

HVAC Sales Master
Green FLASH / Red ON
Pressure switch open fault (does not close during inducer run)
This code typically points to
  • Blocked vent or intake
  • Inducer not creating sufficient draft
  • Split or pinched pressure tubing
  • Condensate/drain restriction on condensing furnaces
  • Failed pressure switch

Next checks to confirm
  1. Verify inducer operation and actual draft
  2. Inspect pressure tubing/ports and condensate path
  3. Verify actual pressure-switch closure under call

Escalation
If inducer draft and venting prove normal but switch never closes, switch or board input is likely.
Reset behavior
Clears when proof is restored; repeated ignition failures can escalate into 1-hour lockout.
Urgent
Fix now
Source
Nordyne/UTEC fault table