Fault Code Lookup

HVAC Sales Master
2+7
Low pressure switch opened during ignition trial or heating demand
This code typically points to
  • Marginal venting
  • Wind effect
  • Intermittent inducer performance
  • Condensate restriction

Next checks to confirm
  1. Verify switch remains closed through ignition and run
  2. Check vent, intake, and condensate path
  3. Measure running pressure in inches w.c.

Escalation
Recycle / retry behavior; may lead to watchguard
Reset behavior
Clears when pressure switch remains proven during a successful heat call.
Urgent
Fix now
Source
Lennox G61MPV diagnostic table, p.63