HVAC Sales Master
2+3
Low pressure switch failed open
This code typically points to
  • Vent restriction
  • Weak inducer
  • Tubing leak or water in tubing
  • Condensate trap blockage

Next checks to confirm
  1. Verify inducer energizes
  2. Verify pressure switch closes within allowed proving period
  3. Per ML180UH public sequence, 2.5 minutes to prove then pressure-switch watchguard starts with 5-minute reset period
  4. Measure operating pressure in inches w.c. at the switch

Escalation
Heat sequence aborted; watchguard engages if proving repeatedly missed
Reset behavior
Auto-retry after reset period; manual thermostat interruption also resets sequence path in some branches.
Urgent
Fix now
Source
Lennox G61MPV diagnostic table, p.63; Lennox ML180UH heating sequence, p.40