Fault Code Lookup

HVAC Sales Master
E160
Refrigerant leak detector sensor #1 type incorrect
This code typically points to
  • Wrong sensor type installed

Next checks to confirm
  1. Replace with Lennox-approved sensor
  2. Retest with Low GWP test button

Escalation
Blower latches for a minimum of 5 minutes
Reset behavior
Clears when a suitable sensor is detected.
Safety Critical
Immediate concern
Cross-generation conflict
Codes E150, E151, E152, E154, E155, E160, E161, E163, E164, and E390 only exist on K-revision Lennox furnaces (EL195UHNEK, ML196UHEK). These are refrigerant leak detection codes for R-454B A2L compliance. E154/E155 will latch the blower ON for at least 5 minutes regardless of thermostat call — this is a code-mandated safety behavior. A2L refrigerant detection CANNOT be disabled — it's prohibited by safety codes.
Source
Lennox EL195UHNEK Installation Instructions 508575-01, p.46