E6
Flame sense microamp signal is low
This code typically points to
  • Coated/oxidized flame sensor
  • Flame sensor incorrectly positioned in burner flame
  • Lazy burner flame due to improper gas pressure or combustion air

Next checks to confirm
  1. Clean flame sensor
  2. Inspect sensor alignment
  3. Inspect air inlet piping
  4. Compare gas pressure to rating plate and adjust as needed

Escalation
Furnace may continue to run with reduced flame-sense margin; can progress to ignition failure/lockout
Reset behavior
Clears when flame-sense signal returns to acceptable range.
Service Soon
Schedule repair
Source
DC96VC/DM96VC Service Instructions troubleshooting chart, p.46