E4
Flame sensed with no call for heat
This code typically points to
  • Short to ground in flame-sense circuit
  • Lingering burner flame
  • Slow-closing gas valve

Next checks to confirm
  1. Correct short at flame sensor/flame-sensor wiring
  2. Check for lingering flame
  3. Verify proper gas-valve operation

Escalation
Induced-draft blower and circulator blower run continuously; no furnace operation
Reset behavior
Clears after false-flame condition is removed.
Safety Critical
Immediate concern
Source
DC96VC/DM96VC Service Instructions troubleshooting chart, p.46