Fault Code Lookup

HVAC Sales Master
E3
Primary limit or auxiliary limit circuit is open; rollout limit circuit is open
This code typically points to
  • Insufficient conditioned airflow
  • Blocked filters
  • Restrictive or improper ductwork
  • Blower speed too low
  • Failed blower motor
  • Flame rollout
  • Misaligned burners
  • Blocked flue/air inlet
  • Failed induced-draft blower
  • Loose/improper wiring

Next checks to confirm
  1. Check filters/ductwork
  2. Check circulator blower speed/performance
  3. Check burners for proper alignment
  4. Check flue and inlet piping
  5. Check induced-draft blower
  6. Tighten/correct wiring

Escalation
Circulator blower runs continuously; no furnace operation until limit condition clears
Reset behavior
Clears after the open limit/rollout circuit returns to normal and underlying cause is corrected.
Safety Critical
Immediate concern
Source
DC96VC/DM96VC Service Instructions troubleshooting chart, p.46