E2
Low-stage pressure switch circuit is not closed
This code typically points to
  • Pressure-switch hose blocked/pinched/improperly connected
  • Blocked flue or inlet air pipe
  • Blocked drain system
  • Weak induced-draft blower
  • Incorrect pressure-switch set point or malfunctioning contacts
  • Loose/improperly connected wiring

Next checks to confirm
  1. Inspect pressure-switch hose
  2. Inspect flue and/or inlet air piping for blockage/length/elbows/termination
  3. Check drain system
  4. Check induced-draft blower performance
  5. Correct pressure-switch set point/contact issue
  6. Tighten/correct wiring

Escalation
Induced-draft blower runs continuously with no further furnace operation
Reset behavior
Clears after pressure-switch proving is restored.
Urgent
Fix now
Source
DC96VC/DM96VC Service Instructions troubleshooting chart, p.46