Fault Code Lookup

HVAC Sales Master
E0
Furnace lockout due to excessive number of ignition retries
This code typically points to
  • Failure to establish flame
  • No gas to burners
  • Front cover pressure switch stuck open
  • Bad igniter or igniter alignment
  • Improper orifices
  • Coated/oxidized or improperly connected flame sensor
  • Intermittent gas supply
  • Lazy burner flames from improper gas pressure or restricted flue/combustion air
  • Improper induced-draft blower performance

Next checks to confirm
  1. Locate/correct gas interruption
  2. Check front-cover pressure switch operation and wiring
  3. Replace or realign igniter
  4. Check/clean flame-sense signal
  5. Inspect flue piping for blockage/length/elbows/termination
  6. Verify induced-draft performance

Escalation
Three total ignition tries, then lockout; auto-reset after one hour
Reset behavior
Thermostat off for more than 5 seconds and less than 20 seconds, then back on; or disconnect power for at least 5 seconds; auto-reset after one hour.
Urgent
Fix now
Source
DC96VC/DM96VC Service Instructions, abnormal operation and troubleshooting chart, pp.41, 45