b0
Circulator blower motor is not running when it should be running
This code typically points to
  • Loose wiring connection at blower motor power leads or disconnected leads
  • Open circuit in inductor or loose wiring connection at inductor (3/4 HP and 1 HP models only)
  • Failed circulator blower motor

Next checks to confirm
  1. Tighten/correct wiring connection
  2. Verify continuity through inductor and replace if open/short
  3. Check circulator blower motor and replace if necessary

Escalation
Furnace fails to operate
Reset behavior
Clears after blower-motor power fault is corrected.
Urgent
Fix now
Source
DC96VC/DM96VC Service Instructions troubleshooting chart, p.48