Fault Code Lookup

HVAC Sales Master
58 / E58
Overload protection sensor for compressor is opened
This code typically points to
  • Overload protection sensor inoperable
  • Jumper wire (X33A) in incorrect position or off

Next checks to confirm
  1. Check resistance on OL sensor
  2. Replace if needed
  3. Check OL sensor position on compressor body
  4. Check jumper-wire position (X33A)

Escalation
Compressor protection fault
Reset behavior
Clears after overload sensor/jumper condition is corrected.
Urgent
Fix now
Source
Daikin Fit Outdoor Unit Installation Manual 3P515859-5S, troubleshooting table, p.37