34 / E34
Control board detected a high current condition; indicates potential short circuit
This code typically points to
  • Current spike in supply
  • Stop valve not completely open
  • Compressor wire is lost phase
  • Faulty control board
  • Faulty compressor

Next checks to confirm
  1. Check power supply for in-rush current during startup/steady state
  2. Check stop-valve opening
  3. Check wire between control board and compressor
  4. Replace control board if necessary
  5. Check compressor and repair/replace if needed

Escalation
Outdoor protection fault
Reset behavior
Clears after root cause is corrected.
Urgent
Fix now
Source
Daikin Fit Outdoor Unit Installation Manual 3P515859-5S, troubleshooting table, p.35