178
Indoor unit communication fault / loss of communication with indoor unit (FIELD CONSENSUS — no public OEM definition located)
This code typically points to
  • ABCD communication bus issue
  • Failed indoor board dragging down the bus
  • High-resistance or shorted comm wiring
  • Intermittent power loss to indoor unit

Next checks to confirm
  1. Start at the wall control and work inward
  2. Verify indoor unit power first
  3. Then ABCD bus continuity/polarity/shorts
  4. Then isolate indoor board vs wiring

Escalation
No public OEM escalation rule found. Treat as event/fault surfaced by wall control rather than publicly documented timed lockout family.
Reset behavior
Often clears after restoring communication and power-cycling. May recur if indoor board or bus wiring remains unstable.
Urgent
Fix now
Need deeper detail?
Retrieve the subcode for this platform:
  1. From the main screen, touch Menu
  2. Touch and hold the Service icon for at least 10 seconds until it turns green
  3. Open Service Information
  4. Use View Diagnostics for the most recent fault's top three likely root causes
  5. Use Last 10 System Events for timestamped recent events
  6. Use Run/Fault History for resettable fault counters, cycle counters, and run times
Source
Field consensus — distributor training, field discussions, non-OEM Bryant Connex explainer. Not found in public Carrier/Bryant OEM manual set.