Fault Code Lookup

HVAC Sales Master
ON SOLID
Control locked out, auto-reset after 1 hour, possible gas valve relay stuck open / flame sense circuit failure / software check error
This code typically points to
  • Fuse/wiring fault
  • Control fault
  • Flame-sense circuit failure

Next checks to confirm
  1. Verify 115V, 24V at SEC-1/SEC-2, fuse, and model plug
  2. If ON SOLID repeats after reset, condemn control

Escalation
Replace control if repeating immediately after reset.
Reset behavior
Auto-reset after 1 hour for ON SOLID.
Urgent
Fix now
Source
OEM service label / flow chart