OFF
Secondary voltage fuse is open
This code typically points to
  • Short circuit in secondary-voltage (24VAC) wiring

Next checks to confirm
  1. Inspect 24VAC circuit for shorts before replacing fuse
  2. Replace fuse and disconnect thermostat leads to isolate short circuit

Escalation
Escalate only after isolating field low-voltage wiring and accessories if fuse continues to open.
Reset behavior
Restores when short is corrected and fuse is replaced.
Urgent
Fix now
Source
ICP (F/G)9MVE A3/A4 Service Manual Figure 15 Service Label and Figure 17 Troubleshooting Guide