6
Flame not sensed during trial for ignition, or flame signal lost during blower-on delay
This code typically points to
  • Gas valve off
  • Manual shutoff valve
  • Missing green/yellow ground wire to furnace sheet metal
  • Grounded flame sensor
  • Oxide buildup on flame sensor
  • Inadequate flame carryover/rough ignition
  • Defective HSI
  • Low inlet gas pressure

Next checks to confirm
  1. OEM sequence: component test for igniter
  2. Verify 115V to igniter
  3. Verify 24V to gas valve
  4. Observe burner ignition/stability
  5. Measure flame current

Escalation
If four attempts fail, progresses to 6+1.
Reset behavior
Repeats ignition sequence 3 more times before 6+1 lockout.
Urgent
Fix now