4+3
Low-heat pressure switch open while high-heat pressure switch is closed
This code typically points to
  • Plugged condensate drain
  • Low inlet gas pressure if LGPS used
  • Improper pressure-switch wiring
  • Water in vent piping, possibly sagging pipe
  • Disconnected or obstructed pressure tubing
  • Stuck open low-heat pressure switch

Next checks to confirm
  1. Check condensate drainage first
  2. Verify inlet gas pressure if low-gas-pressure switch is used
  3. Inspect pressure-switch wiring
  4. Inspect vent piping for water/sagging
  5. Inspect pressure tubing for disconnection or obstruction
  6. Test low-heat pressure switch for open/stuck-open condition

Escalation
Escalate to control/pressure-proving circuit diagnosis only after condensate, venting, tubing, wiring, gas-pressure, and low-heat switch condition are verified.
Reset behavior
No distinct timed auto-reset; treat as active status that should clear when contradictory pressure-switch condition is corrected.
Urgent
Fix now
Source
ICP (F/G)9MVE A3/A4 Service Manual Figure 15 Service Label