34.1
Ignition proving failure
This code typically points to
  • Adequate flame sense not detected during trial for ignition
  • Dirty flame sensor, weak ground, low gas pressure, bad gas valve, burner carryover issue

Next checks to confirm
  1. Verify flame is actually lighting
  2. Verify flame-sense current and clean sensor
  3. Verify gas pressure and ground continuity

Escalation
Repeated 34.1 after proper flame current and gas checks points toward control/valve faults.
Reset behavior
Repeated proving failures escalate to 14.1 lockout.
Urgent
Fix now
Source
Carrier-family public snippet on newer major.minor platform