Fault Code Lookup

HVAC Sales Master
24
Secondary voltage fuse open
This code typically points to
  • Short in 24V thermostat/accessory wiring
  • Shorted outdoor-contact circuit
  • Shorted humidifier/accessory
  • Board fuse blown during service or install

Next checks to confirm
  1. Isolate low-voltage wiring
  2. Inspect thermostat, outdoor, and accessory circuits
  3. Replace fuse only after fault isolation

Escalation
Repeated fuse failures after field wiring isolation raise suspicion of board/transformer issue.
Reset behavior
Clears after fuse replacement and fault correction.
Urgent
Fix now
Source
Carrier 58-06T index entry