Fault Code Lookup

HVAC Sales Master
13 red flashes
Second-stage/high pressure switch open with call for second-stage heating
This code typically points to
  • Faulty inducer
  • Blocked vent
  • Broken or disconnected hoses
  • Disconnected pressure-switch or inducer wiring
  • Faulty pressure switch

Next checks to confirm
  1. Verify second-stage inducer/draft path
  2. Inspect tubing and wiring
  3. Use manometer to verify vent pressure

Escalation
Follows active fault logic; clears when proof is correct.
Reset behavior
Clears when proof established.
Urgent
Fix now
Source
TM8Y manual