Fault Code Lookup

HVAC Sales Master
ATL
Ambient Temperature Limited
This code typically points to
  • Outdoor ambient outside allowable range for the current operating mode
  • Thermostat/reversing-valve programming issue
  • Power present on B wire outside during a cooling call

Next checks to confirm
  1. Confirm ambient reading on board display against actual outdoor ambient after 5 minutes idle
  2. If code is latched, remove Y wire and cycle disconnect to view outdoor temperature on display
  3. Replace T4 sensor if displayed ambient is not within 10 degrees F of actual
  4. Confirm ambient is within Bosch published operating thresholds
  5. Verify thermostat/reversing-valve logic for the current mode

Escalation
Operating limitation — no normal operation until ambient or control condition is corrected
Reset behavior
Clears when ambient/control condition is corrected and system is power-cycled or resumes normal operating conditions.
Service Soon
Schedule repair
Need deeper detail?
Retrieve the subcode for this platform:
  1. Connect the IDS system in EasyAir App
  2. Use the contractor view to monitor heat pump health
  3. Review real-time alerts, fault codes, and checkpoint values
  4. For on-site work, use Bluetooth-enabled access to system data and historical fault codes
  5. Calculate superheat/subcool within the app for diagnostic verification
  6. Bluetooth access is retained on-site even without continued remote subscription
Tool required: Bosch EasyAir App
Source
Bosch Air to Air Heat Pump Systems Troubleshooting page, official Bosch public web documentation